Modul compact I/O

ACS INSTAL SRL Timisoara

0724-374104

Detalii

INPUT
Conversion time (analog) approx. 2 ms (per channel)
Sensor supply US 24 V DC (EN 61131-2), max. 200 mA (M12 female), short-circuit and overload protected
Resolution (analog) 15 Bit
Accuracy max. ±0.5 % (of range limit)
INTERNAL COMMUNICATION
Current consumption max. 50 mA
LED display US: sensor supply and internal supply voltage (green: OK); UA: actuator supply (green: OK)
CONNECTIONS
Fieldbus via internal system connection
Sensor-system/actuator supply via internal system connection (max. 2×4 A)
I/O ports M12 (male) 5-pole, A-coded
GENERAL DATA
Protection IP67
Mounting method 2-hole screw mounting
Temperature range 0...+55 °C (storage temperature -20...+75 °C)
Dimensions H × W × D 126×30×34.5 mm
CURRENT INPUT SIGNALS
Load approx. 300 Ohm, differential input
Input range 0...20 mA, 4...20 mA
DIAGNOSTIC
Communication status via LED
Diagnostic via LED per module and channel
Diagnostic via BUS per module and channel
Monitoring - under voltage yes
Monitoring - no voltage yes
Short circuit and overload yes
Actuator warning per channel via LED and BUS
Wire break upper/lower limit overload per channel via LED and BUS
 