Modul I/O

ACS INSTAL SRL Timisoara

0724-374104

Detalii

INTERNAL COMMUNICATION
Current consumption max. 25 mA
CUBE67 SYSTEM SUPPLY
Cube67 system connection max. 10 m
I/O capacity modular Cube20/67 fieldbus station: Cube20 bus node + 15 Cube20/67 modules
Sensor supply US 24 V DC (18...30.2 V DC) EN 61131-2, max. 4 A
Actuator supply UA 24 V DC (18...30.2 V DC) EN 61131-2, max. 4 A
CONNECTIONS
Fieldbus M12 (female) 6-pole
Sensor-system/actuator supply 4 × Spring clamp terminals, max. 2.5 mm² (max. 12 A)
I/O ports 8 × Spring clamp plug-in terminals, max. 2.5 mm²
GENERAL DATA
Protection IP20
Mounting method DIN-rail mountable (EN 60715)
Temperature range 0...+55 °C (storage temperature -20...+85 °C)
Dimensions H × W × D 117×56×47 mm
DIAGNOSTIC
Communication status via LED
 